What is RC1?

What is HUBBOX RC1 Relay Controller?

HUBBOX RC1 is a high-capacity Modbus TCP/IP relay control module developed for industrial automation and building management systems. With 10 digital inputs and 8 relay outputs, it provides an economical and powerful solution for managing large-scale data collection and device control processes from a single central point.

Technical Specifications and Capacity

  • 8-Channel Relay Output: Robust relays capable of switching up to 10A at 230V AC.
  • 10-Channel Digital Input: Wide input voltage support (DC 5-24V) to monitor various sensor and switch signals.
  • Protocol Support: Fully compatible with all PLC, SCADA, and IoT systems via standard Modbus TCP.
  • Communication: 10/100 Mbps Ethernet port for fast and uninterrupted data transmission.
  • Operating Temperature: High reliability in harsh industrial environments ranging from -40°C to +85°C.
  • Rail-Type Enclosure: Plastic rail-type housing design for easy mounting in standard industrial panels.

Modbus Poll Connection Guide

You can use the Modbus Poll software to test the HUBBOX RC1 and monitor the status of its inputs and outputs. Apply the following parameters for connection:

Default Network Settings:
• IP Address: 192.168.24.251
• Subnet Mask: 255.255.255.0
• Modbus Port: 502

Step-by-Step Connection Process

  1. In Modbus Poll, click on the "Connection > Connect" menu.
  2. Select the "Modbus TCP/IP" option.
  3. Type 192.168.24.251 into the IP Address field and click the "Connect" button.
  4. To read data, open the "Setup > Read/Write Definition" window.

Modbus Register Address Table

Data Type Address Range Name / Description Access
Coils (01) 1 - 8 Relay Outputs (Out1 - Out8) R/W
Discrete Inputs (02) 10001 - 10010 Digital Inputs (Input1 - Input10) Read Only
Holding Registers (03) 40004 - 40007 Device IP Address Configuration R/W
Holding Registers (03) 40008 - 40011 Subnet Mask Settings R/W

Technical Support and Application Notes

Important Reminder: Relay outputs are rated for 10A. For loads with very high inrush currents, such as large motors, it is recommended to use an external contactor to extend the relay's lifespan.
  • IP Configuration: Changes made to the IP address may require a device restart to become active.
  • LED Status: The LEDs on the device allow you to instantaneously see which relay is energized and which input is receiving a signal.
  • Power Supply: Ensure a suitable power source within the 7V-24V DC range is used for stable operation.

For more technical documentation and support requests, please visit www.hubbox.io/en/products/hubbox-rc1-relay-controller-10in-8out.