CM02 Modbus Table

HUBBOX CM02 Modbus TCP Map

Developer-first, optimized Modbus TCP register map for seamless OT/IT convergence, sensor readings, and current measurement via HUBBOX CM02.

Doc Version: 1.0  |  Source: CM02_MB&PinOut
Type Address Data Type Variable Name Description (Multiplier / Unit) Access
Coils
Coils 1 - 2 bool Out1 - Out2 IO Logic Outputs. Default: 0 R/W
Input Registers (Analog Sensor Data)
Input Registers 30001 - 30002 uint16 CurrentOut1 - CurrentOut2 IO Analog Value (Multiplier: x0.01 | Unit: V) R
Holding Registers (Config & Current Data)
Holding Reg. 40001 - 40002 uint16 CurrentOut1 - CurrentOut2 Current (Amperage) Value (Multiplier: x0.1 | Unit: A) R
Holding Reg. 40018 uint16 ChangeIPCmd 0: Success, 1: ChangeIP R/W
Holding Reg. 40031 - 40032 uint16 HWVer, SWVer Hardware and Software Versions R
Holding Reg. 40033 uint16 CommandReg 0:Success, 1:Fault, 2:FactoryReset, 3:ApplyConfig, 4:Reboot R/W
Holding Reg. 40034 - 40045 uint16 IP, SN, GW Network Octets. e.g. IP: 192.168.24.251 R/W
Holding Reg. 40046 - 40051 uint16 MAC[5] - MAC[0] Physical MAC Address Octets R/W
Holding Reg. 40052 uint16 Inputs18Type 0: OnlyInput, 1: Input&RelayDrive R/W
Holding Reg. 40053 uint16 OutsHoldEnable 0: OutsIsVolatile, 1: OutsIsNonVolatile R/W
Holding Reg. 40054 - 40057 uint16 PWM Config PWMStatus, PWMCmd, DutyCycle(%)[0-100], PWMFrequency (1-50000Hz) R/W