IOR12 Modbus Table

HUBBOX IO12 I/O Gateway Modbus TCP Map

Developer-first, optimized Modbus TCP register map for seamless OT/IT convergence with ERP, MES, and SCADA systems via HUBBOX IO12.

Doc Version: 2440  |  Date: 30.11.2025
Type Address Data Type Variable Name Description Access
Coils
Coils 1 - 8 bool Out1 - Out8 Relay Outputs 1-8. Default: 0 R/W
Discrete Inputs
Discrete 10001 - 10008 bool Input1 - Input8 Digital Input Statuses R
Input Registers (Analog & Counters)
Input 30001 - 30002 uint16 analog input1 - 2 Analog Input Values. Min/Max: 0-4095 R
Input 30019 - 30033
(Odd Addresses)
uint32 101 - 108 Rising Edge Count Rising Edge Counters (Unit: pcs) R
Holding Registers (Configuration)
Holding 40003 uint16 CommandReg 0:Success, 1:Fault, 2:FactoryReset, 3:ApplyConfig, 4:Reboot, 10:Reset All Counters, 11+: Reset Input Counter x R/W
Holding 40004 - 40015 uint16 IP, SN, GW Network Configuration Octets. e.g. 192.168.24.251 R/W
Holding 40024 - 40027 uint16 PWM Config PWMStatus, PWMCmd, DutyCycle(0-100%), PWMFrequency (1-50000Hz) R/W
Holding 40044 - 40045 uint16 Dac1 - Dac2 Dac Channel Out Value (0-4095) R/W